Electrical
(Input)
|
|
Nominal
(ip)
|
72 |
100
|
250 |
300 |
|
Actual
(Vdc)
|
65-
100 |
100-
140
|
230-
280 |
280-
360 |
|
Input
Amps (max)
|
22.3 |
14.5
|
6.3 |
5.2 |
|
Input
Fuse (MDA)
|
25 |
20
|
7 |
6 |
|
Noise
on Input
|
<
50mV
|
|
Electrical (Output)
|
|
Nominal
(op)
|
12
|
24
|
32
|
48
|
|
Output
Volts (DC)
|
13.6
± 0.05
|
27.2
± 0.05
|
36.3
± 0.05
|
54.4
± 0.05
|
|
Output
Adjustment
|
±
0.5 Volts
|
| Output
Amps (cont.) |
60 |
40 |
30 |
20 |
| Output
Amps (max.) |
70 |
45 |
34 |
22.5 |
|
Output
Crowbar
|
16.0
± 0.5 V
|
32.0
± 1.0 V
|
42.7
± 1.3 V
|
63.9
± 2.0 V
|
|
Output
Ripple & Noise
|
<
50mV
|
|
Transient
Response
|
<
2V for 50% Surge
|
| Switching
Frequency |
60
± 2 KHz |
| Idle
Power |
<
10 Watts |
|
Regulation
(Line & Load)
|
<
+/- 0.5%
|
|
Duty
Cycle
|
Peak
20% for 5 min max
Continuous 100% for 24 hours per day
|
|
Efficiency
|
>
85% @ Maximum Output
|
|
Mechanical and Environmental
|
|
Operating
Temperature
Range
|
-25
to +40°C @ Maximum Output
Derate Linearly 2.5% per °C from 40°C
(Optional -40°C extra wide temperature operation
avail.)
|
|
Humidity
|
0-95°C
Relative Humidity
(non-condensing) with optional conformal coating
|
|
Audible
Noise
|
NONE
Ødb @ 3 feet (34.5 dB when fan operating)
|
|
Typical
Service Life
|
>10
years (87,600 hours)
|
|
Isolation
|
Input-Case
& Input-Output 1500 VDC,
Output-Case 500VDC
|
|
Length
|
14.5
in / 36.8 cm
|
|
Width
|
10.2
in / 25.9 cm
|
|
Height
|
5.5
in / 14.0 cm
|
|
Clearance
|
1
Inch (2.5 cm) all around
|
|
Material
|
Marine
Grade Aluminum
|
|
Finish
|
Black
Anodize / Powder Epoxy Coat
|
|
Fastenings
|
All
18-8 Stainless Steel
|
|
Weight
|
12.0 lb / 5.5 kg
|
|
Connections
|
Four
contact output terminals
|
|
Warranty
|
3
years
|
|
Safety
|
Approval
to cETLus Standards Pending
|