Input
Voltage
|
48V,
125V, 270VDC +/-20% are standard
Other inputs available, please consult factory |
| Input
Protection |
Thermal
fuse, Inrush current limiting, Reverse polarity
protection |
| Isolation |
Input
to chassis 500VDC for < 60V input, 1500VDC for
> 60V input
Input to output 2250VDC, Output to chassis 2250VDC |
| Output
Voltage |
115VAC/60Hz
or 400Hz @4.4A
230V/50Hz @2.17A continuous with grounded neutral
Isolated floating output optional (Consult factory
for other voltages and frequencies) |
| Wave
Form |
Sinusoidal |
| Total
Harmonic Distortion |
Less
than 5% at full load |
| Efficiency |
Min
78% at full load |
| Line
Regulation |
Maximum
0.5% |
| Load
Regulation |
Maximum
± 6% from 10% load to full load ( ±
1% option available) |
| Output
Protection |
Current
limiting with short circuit protection, thermal
shutdown with automatic recovery in case of continuous
overload or insufficient airflow |
| EMI |
Meets
EN 55022 Class B |
| Load
Crest Factor |
Maximum
3.0 at 90% load |
| Operating
Temperature Range |
0°C
to +50°C |
| Humidity |
5
- 95% non-condensing |
| Temperature
Drift |
0.05%
per °C over operating temperature range |
| Dimensions |
5.3"
x 5" x 15.5" Enclosed case (H x W x L) |
| Connections |
Input:
Compression-type terminal
Output: Standard AC receptacle |
| Weight |
9
pounds (4 kg) |
| Safety |
Compliance
to C22.2 No. 107.1 - 01 and UL 458 |
| Options |
Output
Fail Alarm (Form C)
Remote Inhibit: By closing external contacts on
the inhibit terminals |