IVS4000R 19" Rackmount Inverter Detailed Specifications
Input Voltage
24V, 32V, 36V, 48V, 125V, 250VDC +/-20% are standard
Other inputs available, please consult factory
Input Protection
Thermal fuse, Inrush current limiting, Reverse polarity protection
Isolation
For 125VDC input version: 2250VDC input to output; 1700VDC input to chassis; 2250VDC output to chassis
For 250VDC input version: 2250VDC input to output; 2400VDC input to chassis2250VDC output to chassis
Output Voltage
115Vrms / 34Arms OR
220VAC/ 18A (50 or 60Hz standard) with grounded neutral
Isolated floating output optional
(Consult factory for other voltages and frequencies)
Wave Form
Sinusoidal
Total Harmonic Distortion
Less than 5% at full load
Efficiency
Min 82% at full load
Line Regulation
Maximum 0.5%
Load Regulation
Maximum ± 6% from 10% load to full load ( ± 1% option available)
Output Noise High frequency ripple is better than 500mV rms (20MHz BW)
Output Protection
Current limiting with short circuit protection
Thermal shutdown with automatic recovery in case of continuous overload or insufficient airflow
RFI Suppression
Meets requirements of EN55022, Class A conducted emissions
as a minimum

Output Over-voltage Protection
By internal supply voltage limiting at 140VAC on output
Output Over-load Protection:
Hiccup at 6,000W
Load Crest Factor Maximum 2.5 at 90% load
Operating Temperature Range
0°C to +50°C

Humidity
5 - 95% non-condensing
Temperature Drift
0.05% per °C over operating temperature range
Dimensions
6U x 19" rack-mount enclosure / Depth is 16" maximum

Connections
Input: Compression-type terminal
Output: Standard AC receptacle
Weight 53 pounds (24.1 kg)
Safety
Compliance to C22.2 No. 107.1 - 01 and UL 458

Warranty: Twenty Four Months subject to application within good engineering practice
Enhancements to these general specifications can be accommodated upon request
Designed to meet common approval requirements. Specifications Subject to Change Without Notice
Designed and Manufactured in Canada