Input Voltage
|
24V, 32V, 36V, 48V, 125V, 270VDC +/-20% are standard
Other inputs available, please consult factory
|
|
Input Protection
|
Thermal fuse, Inrush current limiting, Reverse
polarity protection
|
|
Isolation
|
1400VDC input to output, input to chassis
500VDC output to chassis
|
|
Output Voltage
|
115V rms / 26A rms OR
220VAC / 13.6A (50 or 60Hz standard)
Consult factory for other voltages and frequencies
|
|
Wave Form
|
Sinusoidal
|
|
Total Harmonic Distortion
|
Less than 5% at full load
|
|
Efficiency
|
Min 78% at full load
|
|
Line Regulation
|
Maximum 0.5%
|
|
Load Regulation
|
Maximum ± 6% from 10% load to full load
( ± 1% option available)
|
| Output
Noise |
High
frequency ripple is better than 500mV rms (20MHz
BW)
|
|
Output Protection
|
Current limiting with short circuit protection
Thermal shutdown with automatic recovery in case
of continuous overload or insufficient airflow
|
|
RFI Suppression
|
Meets requirements of EN55022, Class A conducted
emissions
as a minimum
|
|
Output Over-voltage Protection
|
By internal supply voltage limiting at 140VAC
on output
|
|
Output Over-load Protection:
|
Hiccup at 6,000W
|
| Load
Crest Factor |
Maximum
2.5 at 90% load
|
|
Operating
Temperature Range
|
0°C to +50°C
|
|
Humidity
|
5 - 95% non-condensing
|
|
Temperature Drift
|
0.05% per °C over operating temperature range
|
|
Dimensions
|
8U x 19" rack-mount enclosure
Depth is 17" maximum
|
|
Connections
|
Input: Compression-type terminal
Output: Standard AC receptacle
|
| Weight |
55
pounds (31.8 Kg)
|
|
Safety
|
Compliance to C22.2 No. 107.1 - 01 and UL 458
|