Input Voltage
|
24V, 32V, 36V, 48V, 125V, 270VDC +/-20% are standard
Other inputs available, please consult factory
|
|
Input Protection
|
Thermal fuse, Inrush current limiting, Reverse
polarity protection
|
|
Isolation
|
Input to chassis 500VDC for < 60V input
1500VDC for > 60V input
Input to output 2250VDC
Output to chassis 2250VDC
|
|
Output Voltage
|
115VAC / 60Hz /17A OR
220VAC/50Hz / 9A continuous with grounded neutral
Isolated floating output optional
(Consult factory for other voltages and frequencies)
|
|
Wave Form
|
Sinusoidal
|
|
Total Harmonic Distortion
|
Less than 5% at full load
|
|
Efficiency
|
Min 78% at full load
|
|
Line Regulation
|
Maximum 0.5%
|
|
Load Regulation
|
Maximum ± 6% from 10% load to full load
( ± 1% option available)
|
|
Output Protection
|
Current limiting with short circuit protection,
thermal shutdown with automatic recovery in case
of continuous overload or insufficient airflow
|
|
EMI
|
Meets EN 55022 Class B
|
|
Load Crest Factor
|
Maximum 3.0 at 90% load
Extended range available (Consult factory)
|
|
Operating Temperature Range
|
0°C to +50°C
|
| Humidity |
5
- 95% non-condensing
|
|
Temperature Drift
|
0.05% per °C over operating temperature range
|
|
Dimensions
|
5.3" X 13.8" x 16.75"
(H x L x W) enclosed case
|
|
Connections
|
Input: Compression-type terminal
Output: Standard AC receptacle
|
|
Weight
|
30 pounds (13.64 kg)
|
|
Safety
|
Compliance to C22.2 No. 107.1 - 01 and UL 458
|
|
Options
|
Output Fail Alarm (Form C)
Remote Inhibit: By connecting DC voltage (as specified)
to the inhibit terminals
|