Input Voltage
|
115VAC or 230VAC - 47-63Hz
|
|
Output Voltage
|
115 VAC @ max. 5kW OR
230VAC @ max. 10kW
|
|
Input Isolation
|
2250VDC line to chassis
|
|
Transfer time
|
8ms max
|
|
Contact Breaking Capacity
|
300A RMS
|
|
Contact Making Capacity
|
500A RMS
|
|
Continuous Current Capacity
|
50A RMS
|
|
EMI Suppression
|
EN 55022 Class A as a minimum
|
|
Input connections
|
Compression type terminal block
|
|
Output connections
|
Compression type terminal block or six standard
outlets
|
|
Alarms
|
Utility fail
Inverter fail
Potential-free form C with acoustic indicator
for both alarms
|
|
Visual Indicators
|
LEDs to indicate whether the load Is being supplied
from the inverter input or the utility input
|
|
Operating Temperature Range
|
0°C to +50°C
|
| Storage
Temperature |
-55
to 85 oC
|
|
Dimensions
|
2U (3.5") x 19" x 15"
|