BCD601 DC/DC Battery Equalizer Detailed Specifications

Model

BCD601-24-12

Electrical
Input Volts (DC) 20 - 30
Input Amps (max) 30
Output Volts (DC) Input Volts / 2 ± 0.05 V
Charging Amps 50
Output Crowbar 16.0 ± 0.5 V
Input Fuse (AGC)
2 x 20A
Output Fuses (AGC) 2 x 30A
Low Input Voltage Alarm 21.0 VDC
Battery Banks 1
Stages 2
Noise on Input < 50 mV
Noise on Output < 50 mV
Battery Size (Amp Hours) 200 - 300
Transient Response < 1V for 15A Surge
Efficiency > 85 % @ maximum output
Duty Cycle Continuous 100% for 24 hours per day
Regulation (Line & Load) < +/- 0.5%

Mechanical and Environmental
Operating Temperature Range -25° to +40° C @ Maximum Output
Derate Linearly 2.5% per °C from 40°C
(Optional -40°C extra wide-temperative available)
Humidity 0-95°C Relative Humidity
(non-condensing) with optional conformal coating
Audible Noise NONE Ødb @ 3 feet
Typical Service Life >10 years (87,600 hours)
Isolation Any Input or Output to Case 500 VDC,
Input to Output - Common Negative
Length 9.1 in / 23.1 cm
Width 7.8 in / 19.8 cm
Height 4.3 in / 10.8 cm
Clearance 1 Inch (2.5 cm) all around
Material Marine Grade Aluminum
Finish Black Anodize / Powder Epoxy Coat
Fastenings All 18-8 Stainless Steel
Weight 6.0 lb / 2.7kg.
Connections Four contact output terminal
Warranty 3 years

Enhancements to these general specifications can be accommodated upon request
Designed to meet common approval requirements. Specifications Subject to Change Without Notice
Designed and Manufactured in Canada