Electrical
(Input)
|
|
Nominal
(ip)
|
24 |
48
|
|
Actual
(Vdc)
|
20
- 35 |
40
- 60 |
|
Input
Amps (max)
|
20 |
9.6 |
|
Input
Fuse (MDA)
|
MDA25 |
MDA15 |
|
Noise
on Input
|
<
25mV
|
|
Electrical
(Output)
|
|
Nominal
(op)
|
12
|
24
|
48
|
|
Output
Volts (DC)
|
13.6
± 0.05
|
27.2
± 0.05
|
54.4
± 0.05
|
|
Absorption
Voltage (Vdc)
|
14.4
|
28.8
|
57.6
|
|
Charging
Amps
|
20
|
10
|
5
|
|
Absorption
to Float
|
3.0
Amps
|
1.5
Amps
|
1.0
Amps
|
|
Output
Fuses (AGC)
|
25 x 2
|
15
x 2
|
10
x 2
|
|
Battery
Banks
|
1
or 2
|
| Output
Adjustment |
±
0.5V |
|
Battery
Size (Amp Hours)
|
80
- 120
|
40
- 60
|
20
- 30
|
|
Output
Crowbar
|
16.0
± 0.5 V
|
32.0
± 1.0 V
|
63.9
± 2.0 V
|
|
Temperature
Compensation
|
-30
mV/°C
|
-60
mV/°C
|
-120
mV/°C
|
|
Output
Ripple & Noise
|
<
25mV
|
|
Transient
Response
|
<
2V for 50% Surge
|
|
Regulation
(Line & Load)
|
<
+/- 0.5%
|
|
Duty
Cycle
|
Continuous
100% for 24 hours per day
|
|
Efficiency
|
>
75% @ Maximum Output
|
| Stages |
2
or 3 (User Selectable) |
|
Mechanical and Environmental
|
|
Operating
Temperature
Range
|
-25
to +40°C @ Maximum Output
Derate Linearly 2.5% per °C from 40°C
(Optional -40°C extra wide temperature operation
avail.)
|
|
Humidity
|
0-95°C
Relative Humidity
(non-condensing) with optional conformal coating
|
|
Audible
Noise
|
NONE
Ødb @ 3 feet
|
|
Typical
Service Life
|
>10
years (87,600 hours)
|
|
Isolation
|
Input-Case
& Input-Output 1500 VDC,
Output-Case 500VDC
|
|
Length
|
9.6
in / 24.4 cm
|
|
Width
|
8.2
in / 20.8 cm
|
|
Height
|
3.5
in / 6.4 cm
|
|
Clearance
|
1
Inch (2.5 cm) all around
|
|
Material
|
Marine
Grade Aluminum
|
|
Finish
|
Black
Anodize / Powder Epoxy Coat
|
|
Fastenings
|
All
18-8 Stainless Steel
|
|
Weight
|
7.5 lb / 3.4 kg
|
|
Connections
|
Four
contact output terminal
|
|
Warranty
|
3
years
|
|
Safety
|
UL458
& CSA 22.2.107.1 Pending
|