Model
|
BCD300-32-12
|
BCD300-32-24
|
Electrical |
| Input
Volts (DC) |
20
- 45 |
30
- 45 |
| Input
Amps (max) |
20 |
22 |
| Output
Volts (DC) |
13.6
± 0.05 V |
27.2
± 0.05 V |
| Charging
Amps |
25 |
20 |
| Output
Crowbar |
16.0
± 0.5 V |
32.0
± 1.0 V |
| Input
Fuses |
AGC
25 Amp
|
| Output
Fuses |
AGC
30 Amp x 2 |
AGC
25 Amp x 2 |
| Low
Input Voltage Alarm |
10.5
VDC |
| Output
Adjustment |
±
0.5V |
| Battery
Banks |
1
or 2 |
| Stages |
2 |
| Noise
on Input |
<
10 mV |
| Noise
on Output |
<
10 mV |
| Battery
Size (Amp Hours) |
100
- 150 |
80
- 120 |
| Transient
Response |
<
1V for 15A Surge |
| Efficiency |
>
90 % @ maximum output |
| Duty
Cycle |
Continuous
100% for 24 hours per day |
| Regulation
(Line & Load) |
<
+/- 0.5% |
Mechanical and Environmental |
| Operating
Temperature Range |
-25°
to +40°C @ Maximum Output
Derate Linearly 2.5% per °C from 40°C
(Optional -40°C extra wide temperature operation
avail.) |
| Humidity |
0-95°C
Relative Humidity
(non-condensing) with optional conformal coating |
| Audible
Noise |
NONE
Ødb @ 3 feet |
| Typical
Service Life |
>10
years (87,600 hours) |
| Isolation |
Input-Case
& Input-Output 1500 VDC,
Output-Case 500 VDC |
| Length |
9.1
in / 23.1 cm |
| Width |
7.8
in / 19.8 cm |
| Height |
2.5
in / 6.4 cm |
| Clearance |
1
Inch (2.5 cm) all around |
| Material |
Marine
Grade Aluminum |
| Finish |
Black
Anodize / Powder Epoxy Coat |
| Fastenings |
All
18-8 Stainless Steel |
| Weight |
4.0
lb / 1.8 kg. |
| Connections |
#12
AWG Input Wires (Positive and Negative)
Four contact output terminal |
| Warranty |
3
years |