Electrical (Input)
|
|
Nominal
(ip)
|
72
|
110
|
220
|
250
|
300
|
|
Actual
(Vdc)
|
65-
100
|
100-
140
|
200-
250
|
230-
280
|
280-
360
|
|
Input
Amps (max)
|
21
|
14.4
|
7
|
6.0
|
4.9
|
|
Input
Fuse (MDA)
|
25
|
15
|
7
|
7
|
6
|
|
Noise
on Input
|
<
50mV
|
|
Electrical (Output)
|
|
Nominal
(op)
|
12
|
24
|
32
|
48
|
|
Output
Volts (DC)
|
13.6
± 0.05
|
27.2
± 0.05
|
36.3
± 0.05
|
54.4
± 0.05
|
|
Absorption
Voltage (Vdc)
|
14.4
|
28.8
|
38.4
|
57.6
|
|
Charging
Amps
|
60
|
40
|
30
|
20
|
|
Absorption
to Float
|
6
Amps
|
4
Amps
|
3
Amps
|
2
Amps
|
|
Output
Fuses (ATC)
|
40
x 2
|
40
x 2
|
40
x 2
|
25
x 2
|
|
Battery
Banks
|
1
or 2 (3 Bank Option Available)
|
|
Battery
Size (Amp Hours)
|
240
- 360
|
160
- 240
|
120
- 180
|
80
- 120
|
|
Output
Crowbar
|
16.0
± 0.5 V
|
32.0
± 1.0 V
|
42.7
± 1.5 V
|
63.9
± 2.0 V
|
| Temperature
Compensation |
-30
mV/°C |
-60
mV/°C |
-80
mV/°C |
-120
mV/°C |
|
Output
Ripple & Noise
|
<
50mV
|
|
Transient
Response
|
<
2V for 50% Surge
|
|
Regulation
(Line & Load)
|
<
+/- 0.5%
|
|
Duty
Cycle
|
Continuous
100% for 24 hours per day
|
|
Efficiency
|
>
80% @ Maximum Output
|
| Stages |
2
& 3 (User Selectable) |
|
Mechanical and Environmental
|
|
Operating
Temperature
Range
|
-40°
to +40° C @ Maximum Output
Derate Linearly 2.5% per °C from 40°C
|
|
Humidity
|
0-95°C
Relative Humidity
(non-condensing) with optional conformal coating
|
|
Audible
Noise
|
NONE
Ødb @ 3 feet (34.5 dB when fan operating)
|
|
Typical
Service Life
|
>10
years (87,600 hours)
|
|
Isolation
|
Input-Case
& Input-Output 1500 VDC,
Output-Case 500VDC
|
|
Length
|
14.5
in / 36.8 cm
|
|
Width
|
9.9
in / 25.1 cm
|
|
Height
|
5.5
in / 14.0 cm
|
|
Clearance
|
1
Inch (2.5 cm) all around
|
|
Material
|
Marine
Grade Aluminum
|
|
Finish
|
Black
Anodize / Powder Epoxy Coat
|
|
Fastenings
|
All
18-8 Stainless Steel
|
|
Weight
|
12.0 lb / 5.5 kg
|
|
Connections
|
Four
contact output terminals
|
|
Warranty
|
3
years
|
|
Safety
|
Approval
to cETLus Standards Pending
|