Electrical (Input) |
|
Nominal
Vac (ip)
|
110
|
220
|
|
Actual
(Vac)
|
105
- 125
|
210
- 250
|
|
Input
Amps (max)
|
7.6 |
3.8
|
|
Input
Fuse
|
MDA
10A (Slow Blow)
|
MDA
5A (Slow Blow)
|
|
Input
Frequency
|
45
- 65 Hz
|
|
Noise
on Input
|
<
50mV
|
Electrical (Output) |
| Nominal
(op) |
12
|
24 |
48 |
| Output
Volts (DC) |
13.6
± 0.05
|
27.2
± 0.05 |
54.4
± 0.05 |
| Absorption
Voltage (Vdc) |
14.4
|
28.8 |
57.6 |
| Output
Amps |
40 |
20 |
11 |
| Absorption
to Float |
4
Amps
|
2.2
Amps |
1.1
Amps |
| Output
Fuses (ATC) |
40
x 2
|
30
x 2 |
15
x 2 |
| Battery
Banks |
1
or 2 (3 Bank Option Available) |
| Battery
Size (Amp Hours) |
160
- 240 |
88
- 132 |
44
- 66 |
| Output
Crowbar |
16.0
± 0.5 V |
32.0
± 1.0 V |
63.9
± 2.0 V |
| Output
Ripple & Noise |
<
50mV |
| Transient
Response |
<
2V for 10A Surge
|
| Regulation
(Line & Load) |
<
+/- 0.5%
|
| Duty
Cycle |
Continuous
100% for 24 hours per day
|
| Efficiency
|
>
75% @ Maximum Output
|
Stages
|
2
& 3 (user selectable)
|
Mechanical and Environmental |
Operating
Temperature
Range |
-25
to +40°C @ Maximum Output
Derate Linearly 2.5% per °C from 40°C
(Optional -40°C extra wide temperature operation
avail.)
|
| Humidity |
0-95°C
Relative Humidity
(non-condensing) with optional conformal coating
|
| Audible
Noise |
NONE
Ødb @ 3 feet (34.5 dB when fan operating)
|
| Typical
Service Life |
>10
years (87,600 hours)
|
| Isolation
|
Input-Case
& Input-Output 1500 VDC,
Output-Case 500VDC
|
| Depth |
13.5
in
|
| Width
|
19"
in
|
| Height
|
2u
(3.5 in)
|
| Clearance
|
1
Inch (2.5 cm) all around
|
| Material
|
Marine
Grade Aluminum
|
| Finish
|
Black
Anodize / Powder Epoxy Coat
|
| Fastenings
|
All
18-8 Stainless Steel
|
| Weight
|
7.2 lb / 3.3 kg
|
| Connections |
Four
contact output terminals
|
| Warranty |
3
years
|
| Safety |
cETLus
to UL1012 & CSA22.2 Pending
|