Electrical (Input) |
|
Nominal
Vac (ip)
|
110
|
220
|
|
Actual
(VAC)
|
105
- 125
|
210
- 250
|
|
Input
Amps (max)
|
3.5 |
1.8
|
|
Input
Fuse (MDA)
|
5A
|
3A |
|
Input
Frequency
|
45
- 65 Hz
|
|
Noise
on Input
|
<
25mV
|
Electrical (Output) |
| Nominal
(op) |
12
|
24 |
32
|
48
|
| Output
Volts (DC) |
13.6
± 0.05
|
27.2
± 0.05 |
36.3
± 0.05
|
54.4
± 0.05
|
| Absorption
Voltage (Vdc) |
14.4
|
28.8 |
38.4
|
57.6
|
| Charging
Amps |
20 |
10 |
7.5
|
5
|
| Absorption
to Float |
3.0
Amps
|
1.5
Amps |
1.1
Amps
|
0.8
Amps
|
| Output
Adjustment |
±
0.5V |
| Output
Fuses (ATC) |
25 x 2
|
15 x 2 |
10 x 2 |
10
x 2 |
| Battery
Banks |
1
or 2 (3 Bank Option Available) |
| Battery
Size (Amp Hours)* |
80
- 120 |
40
- 60 |
30
- 45 |
20
- 30 |
| Output
Crowbar |
16.0
± 0.5 V |
32.0
± 1.0 V |
42.7
± 1.3 V |
63.9
± 2.0 V |
| Temperature
Compensation |
-30
mV/°C |
-60
mV/°C |
-80
mV/°C |
-120
mV/°C |
| Output
Ripple & Noise |
<
25mV |
| Transient
Response |
<
2V for 50% Surge
|
| Regulation
(Line & Load) |
<
+/- 0.5%
|
| Duty
Cycle |
Continuous
100% for 24 hours per day
|
| Efficiency
|
>
75% @ Maximum Output
|
Stages
|
2
or 3 (user selectable)
|
Mechanical and Environmental |
Operating
Temperature
Range |
-25
to +40°C @ Maximum Output
Derate Linearly 2.5% per °C from 40°C
(Optional -40°C extra wide temperature operation
avail.)
|
| Humidity |
0-95°C
Relative Humidity
(non-condensing) with optional conformal coating
|
| Audible
Noise |
NONE
Ødb @ 3 feet
|
| Typical
Service Life |
>10
years (87,600 hours)
|
| Isolation
|
Input-Case
& Input-Output 1500 VDC,
Output-Case 500VDC
|
| Length
|
9.6
in / 24.4 cm
|
| Width
|
8.2
in / 20.8 cm
|
| Height
|
3.5
in / 6.4 cm
|
| Clearance
|
1
Inch (2.5 cm) all around
|
| Material
|
Marine
Grade Aluminum
|
| Finish
|
Black
Anodize / Powder Epoxy Coat
|
| Fastenings
|
All
18-8 Stainless Steel
|
| Weight
|
7.5 lb / 3.4 kg
|
| Connections |
Four
contact output terminal
|
| Warranty |
3
years
|
| Safety |
Approval
to cETLus Standards Pending
|