The RVS1000 Series compact, low-profile DC/AC inverter utilizes established design techniques to deliver 1000VA sine wave voltage. Suitable for a wide range of applications, the RVS1000 features full electronic protection, high efficiency and low output noise.


Internal modules are encapsulated within a thermally conductive MIL-spec silicon rubber compound to ensure resistance against shock, vibration, moisture, humidity, salt, fog, dust, and insects. The unit is conduction cooled. Extended operating temperature ranges are available.


The RVS1000 is housed in a 19”x14”x 3” chassis-mount enclosure. The demonstrated MTBF of the unit exceeds 250,000 hours.


Features

  • Input is filtered to EN 55022 Class A (minimum)
  • Low Profile, Compact Size
  • Sinusoidal wave shape
  • 1000VA of output power
  • Full electronic protection
  • Field-proven design topology

Applications

  • Marine / Automotive / RV
  • Electric Utilities and Substations
  • Telecom Power Plants
  • Manufacturing Locations
  • Steel Mills
  • Military Applications (COTS)
  • Industrial Controls
  • OEM Applications
  • Solar / Alternative Power Systems
  • Fuel Cells

Electrical [Input/Output]/ Mechanical Specification
Input Voltage 24V, 36V, 48V, 125V, 250VDC +20% / -15% are standard
Consult factory for other inputs
Input Protection Thermal fuse / Inrush current limiting / Reverse polarity protection
Isolation Input to chassis: 1500VDC / Input to output: 3000VDC/ Output to chassis: 2250VDC
Output Voltage 115VAC @ 8.7A or 230V @ 4.34A continuous at 50, 60 or 400Hz with grounded neutral
Isolated floating output optional
(Consult factory for other output requirements)
Wave Form Sinusoidal
Total Harmonic Distortion Less than 5% at full load
Efficiency Min. 78% at full load
Line Regulation Better than 0.5%
Load Regulation Better than ± 2% from no load to full load
Output Protection Current limiting with short circuit protection, thermal shutdown with
automatic recovery in case of continuous overload or insufficient airflow
EMI EN 55022 Class A as a minimum
Load Crest Factor Maximum 3.0 at 90% load
Operating Temperature Range 0 °C to +50°C (Wider temperature range available)
Humidity 5 - 95% non-condensing
Temperature Drift 0.05% per °C over operating temperature range
Packaging Fully encapsulated and potted internal modules
Dimensions 19” x 14” x 3” enclosed case
Connections Input/output: compression-type terminal block
(Phoenix SMKDS 5/3-9,6)
Weight 27.5 lb (12.48 kg)
Safety Designed to meet C22.2 No. 107.1 - 01, UL 458 , EN60950 and EN50155
Options Output Fail Alarm (Form C) Remote Inhibit: By closing external contacts on the inhibit terminals
Warranty: Twenty Four months subject to application within good engineering practice
Enhancements to these general specifications can be accommodated upon request
Designed to meet common approval requirements. Specifications Subject to Change Without Notice
Designed and Manufactured in Canada

 
Product Catalogue
Analytic Systems Impact Movie

Apr 13, 2012 - Anniston Army Depot Contracy Award to Analytic Systems » PDF icon

Feb 2, 2011 - Analytic Systems Celebrates "Best In Class" Quality Rating from SRC Tec » PDF icon

Feb 2, 2012 - Analytic Systems Provides Power for US Army Tactical Comms » PDF icon

Toll Free: 1-800-668-3884
Tel: 604.946.9981
Fax: 604.946.9983
Email Us
Facebook/Twitter/LinkedIn:
linkedin